CVE-2026-47710
Received Received - Intake

Stack-Buffer-Overflow in BACnet Stack Library

Vulnerability report for CVE-2026-47710, including description, CVSS score, EPSS score, affected products, exploitability, helpful resources, and attack-flow context.

Publication date: 2026-11-12

Last updated on: 2026-11-12

Assigner: GitHub, Inc.

Description

BACnet Stack is a BACnet open source protocol stack C library for embedded systems. Prior to versions 1.4.4, 1.5.1, and 1.6.0, a stack-buffer-overflow can be triggered in the current master branch when a Loop object reads a referenced property through its default timer path and the referenced property is OBJECT_STRUCTURED_VIEW / PROP_DESCRIPTION containing a long attacker-controlled string. This issue has been patched in versions 1.4.4, 1.5.1, and 1.6.0.

CVSS Scores

EPSS Scores

Probability:
Percentile:

Meta Information

Published
2026-11-12
Last Modified
2026-11-12
Generated
2026-11-12
AI Q&A
2026-11-12
EPSS Evaluated
N/A
NVD
EUVD

Affected Vendors & Products

Showing 1 associated CPE
Vendor Product Version / Range
bacnet-stack bacnet_stack to 1.6.0 (exc)

Helpful Resources

Exploitability

CWE
CWE Icon
KEV
KEV Icon
CWE ID Description
CWE-121 A stack-based buffer overflow condition is a condition where the buffer being overwritten is allocated on the stack (i.e., is a local variable or, rarely, a parameter to a function).
CWE-787 The product writes data past the end, or before the beginning, of the intended buffer.

Attack-Flow Graph

AI Quick Actions

Instant insights powered by AI
Executive Summary

CVE-2026-47710 is a stack-buffer-overflow vulnerability in the BACnet Stack library. It occurs when a Loop object reads a referenced property like OBJECT_STRUCTURED_VIEW or PROP_DESCRIPTION containing a long attacker-controlled string through its default timer path. The issue arises because the Loop object uses a fixed 32-byte stack buffer to read the property, which overflows when the string is too long. This flaw was patched in versions 1.4.4, 1.5.1, and 1.6.0.

Detection Guidance

Detecting this vulnerability requires monitoring for crashes in BACnet devices using vulnerable versions of bacnet-stack. Check for repeated crashes in BACnet/IP devices, especially during Device_Timer processing. Inspect logs for stack overflow errors or memory corruption messages. Use network monitoring tools to detect malformed BACnet packets targeting Loop objects with large Structured View descriptions.

Impact Analysis

This vulnerability can lead to a remote unauthenticated denial of service (DoS) attack. An attacker can crash the BACnet server by sending two valid WriteProperty requests to set a long string in a Structured View description and then referencing it in a Loop object. The server crashes during normal processing due to memory corruption from the buffer overflow.

Mitigation Strategies

Upgrade to patched versions (1.4.4, 1.5.1, or 1.6.0) immediately. If upgrading is not possible, implement input validation to reject long strings in OBJECT_STRUCTURED_VIEW/PROP_DESCRIPTION properties. Disable Loop objects if unused. Apply network segmentation to limit BACnet traffic exposure. Monitor for exploitation attempts targeting Loop object references.

Chat Assistant

Ask questions about this CVE
Hi! I’m here to help you understand CVE-2026-47710. Ask me anything about the vulnerability, its impact, or mitigation strategies.
0/70

EPSS Chart

Security Radar

News mentioning this vulnerability
Loading related security news...